브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to create a custom GSM Modem in ION Setup 2.1

Goals and Symptoms

User may want to add a custom GSM modem in the ION Setup modem list, since the particular modem they have is not listed in the default ION Setup modem list.

Causes and Fixes

I. Browse to the ION Setup folder, Drive:\Program Files\Schneider Electric\ION Setup and open the Modem.ini file as shown below.


  • II. Open the Modem.ini file and copy the lines as shown in the below screenshot into a new blank notepad.



    III. Paste it as shown below in a new notepad. You can now rename the [DEFAULT] to [MY GSM] and change the IDENTIFICATION ID to 99.
    IV. Save the notepad as USER.ini. It's VERY important to save it ONLY as USER.ini
    V. Close all windows, open ION Setup, this time you should be able to see your new modem name in the list.
    VI. You will have to fill out all the information in the notepad for the particular GSM modem that you are using, before it can be used.
    VII. Refer to your modem manual or contact the distributor for more setting information of the modem



Document Change History

Date and InitialsComments
2010-Feb-01 DRM* Article was displaying in raw HTML code. I fixed this.

Last Revised: November 26, 2007

Applies To: ION Setup

Public

All content © 1992-2007 Schneider Electric


Legacy KB System (APS) Data: RESL189706 V2.0, Originally authored by KBAdPM on 11/26/2007, Last Edited by DaMi on 02/02/2010
Related ranges: third party devices (modems, converters...), ION Setup 2.1

슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings