Multiple node query works in ION Enterprise Vista but not in Webreach.

Goals and Symptoms

Webreach functionality works for everything except multiple node queries. Webreach gives the following error:

MultipleNodeQuery

Microsoft OLE DB Provider for SQL Servererror '80040c8e'

Error with provideHTML. Error with GenerateHTML. WebReachHistoricalASP in GetQuery: -2147218290 Cannot execute default connection: An error occurred in Execute: 'PML' is not a recognized ODBC vendor clause option.

/ION/Historical/GetLogs.asp, line 51

Causes and Fixes

In ION Enterprise Vista right click on the data viewer experiencing the issue with the toolbox open and go to the Query tab. Choose edit query here. After the screen where the nodes are chosen and the screen to choose the logs appears for each node as shown below.

Check the Advanced log view box shown in the red box above. Choose Finish, ok, and save the Vista diagram. Open up a new webreach screen and the problem should be resolved.

Attachments

(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/d4de634171ece0f0c12575ae001099a2/fl_block_5/0.1AD6?OpenElement&FieldElemFormat=gif)
Date Created: October 29, 2008
Last Revised: May 5, 2009
Public
Original Author: MN
All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL198436 V1.0, Originally authored by MiNe on 05/06/2009, Last Edited by MiNe on 05/06/2009
Related ranges: ION Enterprise V5.5, ION Enterprise V5.6

슈나이더 일렉트릭 Korea

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings