How to link to a module's setup registers in Power Monitoring Expert Designer.

Issue

User wants to link an input of a module to a setup register of another module in PME Designer.

Product Line

Power Monitoring Expert

Environment

Power Monitoring Expert Designer Application

Cause

Designer allows linking module inputs to outputs, but linking directly to setup registers requires a specific method.

Resolution

To link an input of one module to a setup register of another module in Designer:

  1. In Designer, select the input of the module you want to link.
  2. Hold down Ctrl and left-click on the output of the module that contains the setup register.
  3. A list of setup registers will appear.
  4. Choose the desired setup register.
  5. The link is now established.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com