In the EGX300, default channel names for BCPM, BCM, and Acti 9 Smartlink do not update to the Administrator user account's language

Goals and Symptoms

Symptoms
For BCPM, BCM, and Acti 9 Smartlink device types, if custom channel/circuit names have been applied, any default channel/circuit names do not update to the Administrator user account language if the language is changed after one of these devices is added.

This can be observed under Monitoring > Real Time Data > Single Device Pages for the mentioned device types.

Causes and Fixes

Cause


The Administrator user account language is changed after a user has applied changes to any channel/circuit names for the devices above. This occurs because a static configuration file is created after any changes are applied to the channel/circuit names.


Resolution

Follow the steps below to reset the default channel names to the Administrator user account language.

NOTE: The following steps will delete custom channel names, and you will have to re-enter any custom names afterward. Channel names are the only information that is reset.

  1. Launch Windows Explorer, type ftp:// and the IP address of the EGX in the Address text box, then press Enter.
  2. Enter the Administrator user name and password, then press Enter.
  3. Double-click the www folder to open it.
  4. Find the configuration file for the device. The format for the configuration file is [Device Name]_[Local ID].conf.
    NOTE: To find the device's Local ID, go to the EGX300 Setup page and click on Device List.

    1 2
  5. Right-click on the .conf file, then click Delete.
  6. Click Yes to confirm file deletion.

    3


Workaround

Apply custom names to all channels/circuits for these device types.

Legacy KB System (APS) Data: RESL210948 V1.0, Originally authored by MaTh on 03/13/2013, Last Edited by MaTh on 03/13/2013
Related ranges: EGX300

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings