브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What could cause all of the Modbus port lights to flash rapidly on my BM85C bridge mux?

Issue:

What could cause all of the Modbus port lights to flash rapidly on my BM85C bridge mux?

Product Line:

BM85C bridge mux, Modicon

Resolution:

If all of the Modbus port LED's are rapidly flashing simultaneously, check to see if
configuration port dip switches are correctly set. The bridge comes with all the
configuration port switch settings down, the BM85C requires the right/ upper switch to
have switch 8 in the up position. The configuration port switches are recessed and
easy to overlook.

switch positions

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings