오늘 무엇을 도와드릴까요?

How to connect Unity Pro to a Modbus PLC through a TSXETG100 Ethernet gateway

Issue

How can Unity Pro connect to a Modbus PLC through a TSXETG100 Ethernet gateway?

Product Line

  • TSXETG100
  • Unity Pro

Environment

The TSXETG100 is used as the communication gateway between Unity Pro and the PLC.

Resolution

  1. Configure the PLC Modbus address in the TSXETG100

    • Open the TSXETG100 web interface by entering its IP address in a web browser.

ETG0100, connection

      • Log in to the TSXETG100.
      • Select Setup > Device List.

web page, ETG,

      • Add the Modbus address of the PLC to the device list.
      • Select Apply to save the configuration.
  1. Configure the PLC address in Unity Pro

    • Open the Unity Pro project.
    • Select PLC > Set Address.
    • unity Pro, Set address
    • In Media, select TCPIP.
    • In the Address field, enter the TSXETG100 IP address followed by a semicolon (;) and the PLC Modbus address.
    • connection configuration

    In this example:

    • 192.168.40.2 is the TSXETG100 IP address.
    • 1 is the Modbus address of the PLC.
  2. Connect to the PLC

    • Confirm the address configuration.
    • Select PLC > Connect.


슈나이더 일렉트릭 Korea

자세히 알아보기

자세히 알아보기

도움이 필요하신가요?

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.