오늘 무엇을 도와드릴까요?

How to Display a Register Handle in a Meter Using ION Setup

Issue

The customer doesn’t know how to configure an ION meter specific measurement or value by referencing an ION handle (register handle) using ION Setup.

Product Line

ION Setup 3.2

ION meters

PM8000 series meter

Environment

Editing or adding a Display module to show a specific register

Connected to the meter (serial/Ethernet)

Using Advanced ION Setup configuration mode

Cause

ION meters use Display modules to show data on the front panel. Each display item must reference a specific data source using an ION handle by default. The meter display comes with default measurements or values but can be modified if needed using ION Setup Display Modules.

Resolution

  1. Identify the ION handle  that needs to be linked to the Display Modules, so it can be seen in the front display. Like HS Vln avg, … The Modules are seen using ION Setup Advanced Mode.
  2. Open ION Setup

a. Method 1

Right‑click the meter → PropertiesTools tab → use the drop‑down menu to select Show Advanced ION Setup, then click OK. If prompted for a password, enter the default password “0” (if it has never been changed). All ION Setup Modules will then become visible.

Figure 1 : First method to access the ION Setup advanced configuration Mode

Figure 1 : First method to access the ION Setup advanced configuration Mode

b. Method 2

Press and hold down the “Ctrl” key then “Left click” on the meter to make all the ION Setup Modules visible. When finished do the same to exit the ION Setup advanced configuration Mode. Then select the Display Module for either of the scenarios, you get this:

Figure 2: Second Method  to access the ION Setup advanced configuration Mode

Figure 2: Second Method  to access the ION Setup advanced configuration Mode

  1. After entering the password if requested, a new Display module will be created, and you can rename it by right clicking on it.

- >  Double clicks to open it  - > Source 1  - > Edit   - > Navigate the Power Meter modules in this case as an example  - > Select HS Vln avg - > Select the ION handle needed which will appear under parameter  - > then “OK”.

Figure 3: Using the ION Display Module to add  the ION handle to be displayed.

Figure 3: Using the ION Display Module to add  the ION handle to be displayed.

The source is then selected and linked to Source 1. Click “ Send “ to save the configuration to the meter. Once saved, the meter will display data for that ION Handle when available.

Figure 4: Sending the selected ION handle to be displayed to the meter

Figure 4: Sending the selected ION handle to be displayed to the meter

Note :

Best practice

  • Verify unit scaling: Some registers may require scaling or formatting for proper display.
  • Avoid duplicate display lines: Ensure multiple display pages do not reference conflicting handles.
  • Document your changes: Note which display items were modified for future maintenance.
  • Test on meter: Confirm the value appears correctly on the meter’s physical display.

Documentation:

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings