Issue
 Using MBMaster to verify that a Modbus device is working.
 
 Product Line
 Modbus devices
 
 Environment
 Windows
 
 Cause
 MbMaster can be used to determine if a modbus device is working.
 
 Resolution
 Run this program from a DOS prompt.
 
 For example here is a sample where I connect to a 6200 device at 19,200 baud. I am using the PC's COM2. The meter's Unit ID is 100 and it is configured to use the Modbus protocol. I am asking for Modbus address 44000 which provides the password for this meter. My meter's password is 0.
 
 MBMaster provides quite a bit of diagnostic information which you can ignore in this case. Just look for the data from the register.
 
 -=-=-=-=-=- Sample MBMaster -=-=-=-=-=-=-=-
 H:\\Bin>mbmasterV21M3 -COM2 -B19200 -ID100 -SR44000 -NR1
 MBMASTER v2.1M3:    Compiled at Jul 13 2001 04:13:57
 
 Stripped BAUD from input: 19200
 Stripped SR from input: 44000
 Install ModPL
 About to open ModPL with port COM2
 Building request: modslave = 100
 Modbus AL frame received: fc = 03
 Modbus AL frame: startreg = 404000, #regs = 1
 Register 404000: 0
 Exiting.
 -=-=-=-=-=- End Sample MBMaster -=-=-=-=-=-=-=-