브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Quick start for configuring the TCSEGDB23F24FA M340 Modbus Plus Proxy Module.

Issue

Quick start for configuring the 'TCSEGDB23F24FA' M340 Modbus Plus Proxy Module

Product Line
'TCSEGDB23F24FA' M340 Modbus Plus Proxy Module

Environment
Windows 7

Resolution
The following steps can be used to configure the' TCSEGDB23F24FA' M340 Modbus Plus Proxy
Module

  • Set the Modbus Plus address for the bridge using the rotary switch that are located on the back
of the module.
  • Connect to the module using the default MAC derived ethernet address.
  • Enter the default username (USER) and password (USER) to access the configuration/setup
web pages.
  • Click on 'Setup'.
  • Click on 'IP Setup'.
  • Enter the IP address parameters.
  • Click on 'Apply'.
  • Click on 'Save To Flash'.
  • Click on 'IP address' under the section labeled 'M340 Interface'.
  • Enter the IP address parameters.
  • Click on 'Apply'.
  • Click on 'Save To Flash'.
  • Click on 'Register Offsets' under the 'M340 Interface' section.
  • Fill in the appropriate parameters.
  • Select 'Legacy Compatability 0x 4x by 1' if you are communicating to a Modicon PLC.
  • Click on 'Apply'.
  • Click on 'Save To Flash'.
  • If applicable, click on the appropriate sections to be filled in under the section named 'Modbus Plus Peer Cop'

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings