브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
When using a Unity Premium PLC, what function block would I use for retrieving diagnostic information from a Modbus slave device?
Issue:
Function block to use in a Premium PLC for retrieving diagnostic information from a Modbus slave device


Product Line:
Premium PLC, Unity Pro


Resolution:
The SEND_REQ function block is used for retrieving diagnostic and maintenance information from  a Modbus slave device....
Modbus Request
Function Code / Sub Function Code
Communication Function
Exception status
16#07
SEND_REQ
Diagnostics
16#08/16#xx
SEND_REQ
Event counter
16#0B
SEND_REQ
Connection event
16#0C
SEND_REQ
Slave identification
16#11
SEND_REQ
The diagnostics and maintenance information are shown below:
Designation
Function code / sub-function code
Read exception status
16#07
Echo
16#08 / 16#00
Initialize module
16#08 / 16#01
Read the diagnostic registers of the PLC
16#08 / 16#02
Change end of frame delimiter (ASCII mode)
16#08 / 16#03
Switch to listening mode
16#08 / 16#04
Reset counters
16#08 / 16#0A
Number of messages received without CRC error
16#08 / 16#0B
Number of frames received with CRC error
16#08 / 16#0C
Number of exceptional responses
16#08 / 16#0D
Number of messages addressed to the PLC
16#08 / 16#0E
Number of broadcast messages received
16#08 / 16#0F
Number of correct responses
16#08 / 16#10
Number of messages received in listening mode
16#08 / 16#11
Number of invalid characters received
16#08 / 16#12
Read event counter
16#0B
Read connection event
16#0C
Read identification
16#11



슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings