오늘 무엇을 도와드릴까요?

How to release latched contacts on the VAMP 321 relay

Issue

The protection elements on the VAMP 321 relay are configured to latch upon initialization and require manual reset.

Product

VAMP 321 Protection Relay

Environment

  • VAMP 321 relay in operation
  • VAMPset configuration software installed and connected to the relay

Cause

The protection elements are set to latch during startup or after a trip event, requiring manual release to restore normal operation.

Resolution

The latched contacts can be released using either the VAMP 321 front panel or the VAMPset software.

Option 1: Release from the VAMP 321 Front Panel

  1. Navigate through the relay’s front screen menu.
  2. Locate the output matrix or latch release menu.
  3. Execute the command to release (reset) the latched outputs.

Option 2: Release via VAMPset Software

  1. Open VAMPset and connect to the VAMP 321 relay.
  2. Navigate to RELEASE OUTPUT MATRIX LATCHES.
  3. Set Release Latches to Release.
  4. Write (upload) the configuration changes to the relay.

VAMP Set

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings