브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What does the IGBT desaturation HDF fault mean on the ATV61 and ATV71 drives?

Issue:
IGBT desaturation HDF fault on the ATV61 and ATV71 drives.

Product Line:
Altivar ATV61 and ATV71

Environment:
All >90KW

Cause:
Short circuit or grounding on the output phases
Transistor IGBT is shorted out.

Resolution:
-Check the motor insulation and wiring. Use a 1000V Megger and test your motor.

-Run the Transistor test in the Diagnostics menu 1.10:

From the Drive menu,

  1. Scroll down to the Diagnostics menu and press enter
  2. Scroll down to Test Procedures and press enter
  3. highlight Transistor Test and press enter

-Perform a static check on the drive. Refer to this article for details: https://www.se.com/ww/en/faqs/FA173615/

-Try running the drive open circuit:

  1. Turn off OPL (menu 1.8 Fault Management, set OPL to no)
  2. Power down
  3. Disconnect the motor leads
  4. Power up the drive
  5. Running the motor at 20, 40, and 60hz. Check the output voltages (phase to phase) at each speed to see if they are balanced.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings