ION meter data logs are very slow to upload
Issue
Data logs from ION meters are very slow to upload into the ION Enterprise / SPM / PME software.
For devices experiencing this issue the most recent logged data in the database may be several days old even though there is no apparent communication issue with the device.
Product Line
Power Monitoring Expert 8.2
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Power Monitoring Software
Cause
One possible cause of this issue can happen after deleting register names from ION meter modules in the ION Designer.
In Management Console, access the Diagnostics Viewer Log Performance tab, look at the information for the device that is experiencing this issue, you will see that the event log contains many pending records. The Event Log is always LogHandle 0x1000
In the Designer application, it is possible to delete the register labels for a module and send those changes to the meter. In the example below the label for Output Register 6 has been deleted.
When this occurs an event will get logged in the meter's event log with the handle value instead of the label name.
Once this happens, the loginserter service will not be able to process the event and the previous event will be the last event logged in the database.
Since there is a high priority on capturing a meter's event log, the other logs on the device may lag behind as the loginserter service is hanging up on the event log.
Cause 2
Another potential issue is that messages are still filtering into the database via the Microsoft Message Queues. Logged data must filter from the device to the log subsystem router where it is processed via the Microsoft Message Queues. When large amounts of data is incoming to the PME server, there may be throttling of the message queueing which slows down the processing of data. This can happen when many devices are switched on at once or a large amount of data is coming into the database all at once.
You can check the status of the queue by navigating to Computer Management -> Services and Applications -> Message Queueing. Click on Private Queues. The below is what the queue should look like if data has been filtered into the database properly.
Resolution
In order to resolve this issue, you will need to clear the meter's event log.
This can be done in ION Setup by modifying a Setup Register in the device's Event Log Control Module which will reset the logged events. You can then revert the change.
Example: Set the Depth to 0 and send the changes then set the depth back to its previous value and send the changes again. The same procedure can be carried out in Designer.
Resetting the Event log will allow the software to begin uploading the Event log successfully.
It is also suggested to add a register label to the module registers that do not have a name.
Resolution 2
If the queue is full, and begins throttling, users may restart the ION Log Subsystem
Router Service to restart the sorting process from the message queues into the proper tables in the ION_Data database.
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.