Video: How do you set up PID control on the ATV21 and ATV212 drives?

Issue:
PID control setup on ATV21 and ATV212 drives?

Product Line:
Altivar ATV21 and ATV212, S-Flex enclosed.

Environment:
All

Cause:
Setting up PID control on the ATV21 and ATV212 drives.

Resolution:

  1. Press the mode button until you see AUF
  2. Arrow down to F------ and press enter
  3. Find F360 and press enter choose your PID feedback assignment and to activate your PID function
  • 1 for VIA
  • 2 for VIB
4. Set FNOD as your PID set point
  • Set to 3 if you want to use the up and down arrows as your set point.
  • Set to 1 for VIA or 2 for VIB if you want your analog input to be your set point.

Please note: it is not a good idea to set up to set your PID feedback F360 to 1 VIA and your set point  FNOD to 1 VIA.

Basic setup for a 4-20mA signal input for PID feedback would be:
F201=20%  (4mA)
F202=0
F203=100%  (20mA)
F204= 60hz
F360= 1 (enable PID and feedback is VIA 4 to 20mA)
FNOD= 3  (up and down arrows are your set point.

Optional settings:
F362=PID proportional gain
F363= PID integral gain
F380 = 1 for Reverse acting (0 = deactivated)


Ref manual 30072-451-63

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings