How Can I Safely Simulate a Fault on an Altivar Drive to Test Redundant System Operation?

Resolution:

This procedure explains how to safely simulate a drive fault to verify that a redundant system correctly detects the failure and switches to a backup drive. This procedure can be useful as well if customers need to test the behavior of drive when faulted.

Recommended Methods:

Method 1: Output Phase Loss Simulation (Preferred)
This method creates a fault without risking damage to equipment.

  1. Power down the drive.
  2. Disconnect the motor leads from all three drive output terminals.
  3. Verify that Output Phase Loss monitoring is enabled on the drive
    (parameter location varies by model — refer to the drive’s programming manual).
  4. Issue a RUN command with the motor disconnected.

Result:
The drive will detect an output phase loss and generate a fault.
Common fault codes may include OPF, OPF2, EPHO, or similar, depending on the drive model.

Method 2: External Fault via Logic Input

  1. Assign an External Fault function to a logic input.
  2. Trigger the input using a momentary contact closure.

Result:
The drive will immediately fault, allowing you to confirm fault detection and system switchover behavior.

Always follow proper lockout/tagout and safety procedures. Refer to the specific Altivar programming manual for parameter names and locations.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings