Why does the IP address on a PM8ECC change to 2.109.2.110?

Issue

The PM8ECC IP address changes to "2.109.2.110" and the (default) gateway changes to "2.113.2.114".

Product

PM8ECC

Cause

This issue is happening because of the permission right while writing to conditional registers.

One possible reason why this specific IP address (2.109.2.110) is chosen is that the IP Address register is located at register number 622.
The hex equivalent breakdown of the IP is as follows:
2 = 2 hex
109 = 6D hex
26D hex = 621 dec
---------------------
2 = 2 hex
110 = 6E hex
26E hex = 622 dec

Note: the IP register is at address 622.

Resolution

To resolve the issue upgrade the OS firmware to 12.5 or higher.

Access to firmware upgrade instructions, including a how-to video and a link to the latest firmware can be found at:

https://www.se.com/ca/en/faqs/FA237920/

If only the firmware is required, it can be downloaded directly from:

https://www.se.com/ww/en/download/document/PM8xx_V12.5/

Or,

1) Using a internet browser navigate to www.se.com/br>2) select Support, then Download Center from the Green menu bar
3) type "PM800 Series V12.500 Firmware" into the search bar and click on the Search button
4) click on the "PM800 Series V12.500 Firmware" link presented in the search results
5) click on the Download button to start the download and save the file

Note: Also by entering only PM800 and/or keyword search criteria into the search bar, you be find wide variety of PM800 related documents.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings