브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How do I calibrate screen for the Magelis XBTGT / HMIGTO / HMIGTU ?
If you go into the runtime configuration manager of the HMI and under the system tab, there is an option called stylus. Touch the stylus button to begin stylus adjustment with a series of six prompts that display in a counterclockwise sequence on the screen.

1)  When the first cross point displays in the top-left corner of the panel, press the center of the cross where the cross hairs intersect. The cross will disappear and the second cross will display.

2) Touch each of the five remaining crosses as they appear in a counterclockwise sequence.
  • When you touch the Stylus, you must touch the center of each cross mark. If you do not touch the cross-hairs cursor, calibration will not complete successfully.
  • The Stylus calibration will complete successfully when you touch all six cross marks, in sequence, from the first cross at the top-left corner of the panel to the sixth cross at the top-center position.
3) When the Stylus calibration is complete, touch the To Run Mode button to close the Vijeo-Designer Runtime Configuration Menu and restart runtime.





슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings