ION 7350 Sag/Swell not triggered when meter is in Direct Delta Volts Mode
Issue
A Sag or Swell is not triggered in an ION 7350 when the meter is configured in Direct Delta Volts Mode.
Product
ION 7350 Power Meter: All versions of Firmware.
Environment
ION7350 meter connected to Delta system and the voltage mode is set to Delta Direct.
Cause
An issue has been identified in the firmware for the sag/swell module on the ION 7350 meter
Resolution
The Sag/Swell module can be relinked to resolve the issue.
1) Link the Vab, Vbc, and Vca voltage from the High Speed Power Meter Module to V1, V2, and V3 accordingly
a) In Designer, navigate to the Sag/Swell module on the meter.
b) Right click on the input icon
c) Select V1 and then select "HS Vll ab" from the Output of the High Speed Power Meter Module
d) Repeat for V2 and V3
Note if the meter is reused for a Wye system the voltage links will need to be restored to default.
A Sag or Swell is not triggered in an ION 7350 when the meter is configured in Direct Delta Volts Mode.
Product
ION 7350 Power Meter: All versions of Firmware.
Environment
ION7350 meter connected to Delta system and the voltage mode is set to Delta Direct.
Cause
An issue has been identified in the firmware for the sag/swell module on the ION 7350 meter
Resolution
The Sag/Swell module can be relinked to resolve the issue.
1) Link the Vab, Vbc, and Vca voltage from the High Speed Power Meter Module to V1, V2, and V3 accordingly
a) In Designer, navigate to the Sag/Swell module on the meter.
b) Right click on the input icon
c) Select V1 and then select "HS Vll ab" from the Output of the High Speed Power Meter Module
d) Repeat for V2 and V3
Note if the meter is reused for a Wye system the voltage links will need to be restored to default.
게시 대상: 슈나이더 일렉트릭 Korea


도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.