브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What does the CRC1 do on ATV32? What information is it giving us?
Issue:
What does the CRC1 do? What information is it giving us?

Product Line:
ATV32

Environment:
All models. Safety function.

Cause:
None

Resolution:
The CRC1 parameter, is a CRC calculation of the ATV32 safety parameter set.
This CRC1 is calculated by the drive to identify a safety configuration.

Since ATV32 V1.8, it's possible to duplicate only the safety configuration from one ATV32 to another one.
To do this we implement a verification mechanism with this CRC1. This CRC1 value will be used when user want to duplicate safety configuration to another drive.

If the safety is not configured, the drive still generates an internal safety parameter set, The value will be always different from 0 as soon as you will make a connection on a product.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings