브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to end Excel and repgen tasks from the command line

Issue
The system has a large number of process running Excel.exe and possibly repgen.exe
Excel Processes

Product
ION Enterprise 6.0.x
StruxureWare Power Monitoring (SPM) 7.0.x
Power monitoring Expert (PME) 7.2.x, 8.0

Environment
Windows Server 2003, 2008, 2008 R2, 2012, 2012 R2, Windows 7

Cause
At times when "repgen/Reporter" is launched from a scheduled task, the process does not end properly and the task continues to run.

Resolution
1) Create a text file with the following commands

taskkill /f /im "reportgen.exe"
taskkill /f /im "excel.exe"
pause


2) Save this file as batch file 'Filename'.bat

3) Right click on the file and select Run as Administrator

Note:
The above commands will stop all instances of excel and repgen without any prompts. More information about taskkill is included below

TASKKILL [/S system [/U username [/P [password]]]] { [/FI filter] [/PID processid | /IM imagename] } [/T] [/F]

Description:
This tool is used to terminate tasks by process id (PID) or image name.

Parameter List:
/S    system           Specifies the remote system to connect to.

/U    [domain\]user    Specifies the user context under which the command should execute.

/P    [password]       Specifies the password for the given user context. Prompts for input if omitted.

/FI   filter           Applies a filter to select a set of tasks. Allows "*" to be used. ex. imagename eq acme*

/PID  processid        Specifies the PID of the process to be terminated. Use TaskList to get the PID.

/IM   imagename        Specifies the image name of the process to be terminated. Wildcard '*' can be used to specify all tasks or image names.

/T                     Terminates the specified process and any child processes which were started by it.

/F                     Specifies to forcefully terminate the process(es).

/?                     Displays this help message.

Examples:
TASKKILL /IM notepad.exe
TASKKILL /PID 1230 /PID 1241 /PID 1253 /T
TASKKILL /F /IM cmd.exe /T
TASKKILL /F /FI "PID ge 1000" /FI "WINDOWTITLE ne untitle*"
TASKKILL /F /FI "USERNAME eq NT AUTHORITY\SYSTEM" /IM notepad.exe
TASKKILL /S system /U domain\username /FI "USERNAME ne NT*" /IM *
TASKKILL /S system /U username /P password /FI "IMAGENAME eq note*"

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings