브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to setup a PTC alarm without tripping the ATV61 drive?

Article available in these languages: 스페인어

Issue:
PTC alarm installation

Product Line:
Altivar 61, Altivar 71

Environment:
All models, all serial numbers

Cause:
Using PTC probes for motor overload protection, requesting warning indication rather than faulting the VFD

Resolution:
PTC warning can be indicated via a relay output assigned to an Alarm Group.
Example for SW2 switch set to PTC, PTC connected to LI6, R2 indication, Alarm Group 1

1.8 Fault Management
PTC Management - activates the PTC monitoring
LI6 = PTC Probe [PTCL] = Always

Motor Thermal Prot - Inactivates the VFD internal I2T overload protection
Overload Fault Mgt [OLL] = Ignore

1.5 Inputs/Outputs CFG
R2 Configuration - assign relay R2
R2 Assignment [R2] = Alarm Grp1

Alarm Grp1 Definition - activate PTC alarm for the warning group
LI6 = PTC Alarm [PLA] = ON

Important note:  When Overload Fault Mgt [OLL] = Ignore, the motor thermal protection by calculating the I2t is inactive.  The drive will not provide motor overload protection based on motor current.  Both functions can work at the same time by keeping Overload Fault Mgt [OLL] = Freewheel

슈나이더 일렉트릭 Korea

첨부 파일
atv61_programming_manual_en_1760649_08.pdf [4.35 MB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings