브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to resolve error message: "One or more issues occurred with the current version profile. Please contact the vendor to resolve these problems." in Somachine v3.1?
Issue:
How to resolve error message: "One or more issues occurred with the current version profile.  Please contact the vendor to resolve these problems." in Somachine v3.1?

Product Line:
SoMachine

Environment:
PLC Programming Software in Windows

Resolution:
This is an known issue with the installation of SP of Somachine V3.1, when SoMachine was not installed on the default location: "C.\Program Files (x86)\Schneider Electric\SoMachine"

To solve this issue you can move or copy the content of the folder:
"C:\<your installed path>\SoMachine\SoMachine\CoDeSys\PlugIns"
to the correct location
"C:\<your installed path>\Schneider Electric\SoMachine\CoDeSys\PlugIns"

Alternative you can extract and copy the content of the attached zip archive to folder:  "C:\<your installed path>\Schneider Electric\SoMachine\CoDeSys\PlugIns"

Afterward you have to delete the CoDeSys cache file(s) "CoDeSys*.cache" at the following locations: "C:\ProgramData\AP\PlugInCaches\"

슈나이더 일렉트릭 Korea

첨부 파일
UpdatedPlugins.zip [349.18 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings