브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Problem to run soft starter ATS48 in acceleration and deceleration mode even though set the ACC and DEC parameter, need solution?
It is not a problem, but it is the normal behavior of the soft starter. The soft starter is not a speed controller, it is only controlling the torque.

The ACC time and DEC time given in the ATS48 soft starter is for smooth ramp up and ramp down time of "motor torque" and it does not mention speed ramp up time. Hence the speed ramp up time will vary depending upon the load available on the motor. You may refer the screen shots attached below extracted from user manual, it indicates the time setting will ensure smooth increase and decrease of torque as shown in the graph.

acceleration

deceleration

When you start the motor with no-load, 2% to 20% torque may be sufficient to accelerate the motor to full speed, hence the motor will reach full speed faster. The initial torque "T90" parameter is set to 20% as default in factory setting, hence 20% torque will be given immediately after start command and the motor will reach to full speed faster(may be immediately like DOL starter) in no load.

torque

For testing purpose at no load, you may reduce the T90 setting to 0% and increase the ACC and DEC setting to 60 sec(maximum), so that you may find possibly slow ramping of torque, which will help to ramp the speed comparatively slower at no-load.

As a normal commissioning procedure, this T90, ACC and DEC parameters should be set during load trail to get the proper ACC and DEC time duration of speed in normal operation.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings