브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Is it possible to start 3 pumps with one VFD? when pump 1 is running it should put it over to bypass contactor and then start Pump 2 on VFD and then the same for Pump 3?
As per the requirement given above, the VFD will be used only for smooth starting and stopping of the pump. The VFD is not used with pump continuously for energy saving purpose.

It is not recommended to use VFD for the above functional requirement of start and bypass application, because when bypass contactor is ON, the 3 phase input power supply will be connected directly to the drive output through bypass contactor. If input supply is directly connected to the output of VFD, it will damage the IGBT's of the VFD. Refer the highlighted warning screen shot below from ATV61 VFD installation manual.


To avoid direct line supply to VFD output, if we disconnect the VFD output contactor after acceleration to full speed from VFD and command (switch ON) the bypass contactor, it will lead to power disconnection to motor for 1 sec, hence there will be drop in motor speed and hammering effect during change over from VFD to Bypass. Hence this operation with VFD is not recommended.
However ATS48 soft starter can be used to comply the above functional requirement. The customer can use ATS48 soft starter with the control scheme screen shot attached below




슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings