브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Is there a way to automatically logout of an Magelis/Harmony HMI after a time interval of inactivity?
Issue:
Is there a way to automatically logout of an Magelis/Harmony HMI after a time interval of inactivity?

Product Line:
Magelis XBTGC/GK/GT, Harmony HMIGTO/STO/STU, Magelis Smart iPC, Magelis Compact iPC, Magelis Flex Box, Magelis Smart Box, Magelis Compact Box, Harmony Panel PC, Harmony Box PC, Harmony P6, Vijeo Designer

Environment:
Vijeo Designer Runtime on HMI

Resolution:
Yes, you can set the Magelis/Harmony HMI to log out after an inactivity time.  That setting is in the Security Properties under Inactivity Time-out of the Logout Behavior.

Please see below screenshot for more information.

Vijeo Designer Buildtime Project Navigator > Environment > Security settings

The value of the Inactivity Time-Out is in minutes.  When downloading to the target, you will need to check the box to delete the "preserve runtime data" to update the security settings.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings