브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What is the replacement for the High HP ATS01N softstarters?
Issue:
Part number for the replacement of the ATS01N High HP Soft Starters.

Product line:
ATS01, Altistart 01, High HP

Environment:
All models

Cause:
The launch of the ATS22 in 2011 caused the High HP units to become redundant.

Resolution:

The ATS01 High HP units were replaced with the ATS22 units.  These are functional replacements only.  The ATS01 had no overload protection, an internal power supply and simple dial adjustments.  The ATS22 will require external 120V or 230V power.  There are no dials to adjust, but the unit will need to be programmed.  See the ATS22 User Manual, document BBV51330 to review the wiring, dimensions and programming.  See the attached file.

ATS01N230LY - 32A rated.  Replaced by ATS22D32S6U
ATS01N244LY - 44A rated.  Replaced by ATS22D47S6U
ATS01N272LY - 72A rated.  Replaced by ATS22D75S6U
ATS01N285LY - 85A rated.  Replaced by ATS22D88S6U

슈나이더 일렉트릭 Korea

첨부 파일
Install BBV51330_04 ATS22.pdf [5.94 MB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings