브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How do you insert/remove the PCMCIA memory card from the Modicon Premium PLC?
Issue:
How do you insert/remove the PCMCIA memory card from the Modicon Premium PLC?

Product Line:
TSXP57, TSX Premium

Environment:
Memory card on PLC

Resolution:
A PCMCIA memory card handle is required to insert the memory card in its slot.  The Premium controller must be powered off when inserting or removing of the PCMCIA memory card.

Fitting the handle onto the card (see image below):
Fitting handle to card
1. Position the end of the memory card (opposite end from the connector) at the handle opening.
The triangular-shaped markers on both the handle and the label of the card should be on the same side.

2. Slide the memory card into the handle until it stops. It then forms an integral part of the handle.


Inserting the memory card
To install the memory card in the processor, proceed as follows :
Memory Card insertion
1. Remove the protective cover by unlocking and then pulling it towards the front of the PLC,

2. Position the PCMCIA card with its handle into the slot which is now vacant. Slide in until the
card stops, then push the handle to connect the card.

Removing the memory card
1. Pull out the memory card and insert either the slot cover or memory card handle back into the slot.


Note :
When installing the PCMCIA card in its slot, make sure that the physical locating devices are correctly positioned :
• 1 ridge towards the top,
• 2 ridges towards the bottom

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings