브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Why am I unable to change Encoder parameters in my ATV71 drive via SoMove?
Issue:
ATV71 drive with encoder card.  When the drive is in I/O profile, SoMove will occasionally not allow parameters related to the encoder to be changed.

Product Line:
Altivar 71 series drives with encoder cards installed.

Environment:
ATV71 drives in I/O profile with encoder cards installed, SoMove V2.0

Cause:
This is an issue with SoMove software that had not previously been reported.

Resolution:
A permanent fix is being worked on to be released in a later update to SoMove.  A temporary work around is to place the drive into Separate Profile, then back into I/O Profile.  This should allow encoder parameter to be changed via SoMove.  Note that the parameters can still be changed via the keypad normally.  This problem only occurs when using SoMove software to program the drive and is a problem with the SoMove software itself, not with the drive.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings