오늘 무엇을 도와드릴까요?

What is the activation of current overload (OIL) on the ATS48?

Issue:
Current overload (OIL) function on the ATS48.

Product Line:
ATS48

Environment:
All models

Cause:
N/A

Resolution:
In the PrO menu, the (OIL) function is used to either fault the ATS48 or provide an alarm via internal bit or relay output when the motor current exceeds a specified threshold for a specified time.  Set the corresponding parameters:
Current overload threshold (LOC) is adjustable from 50% to 300% of the Nominal motor current (In).
Current overload time (tOL) is adjustable from 0.1 to 60s.

The softstarter always monitors the current, but the OIL function only applies when running at steady state.  When the overload conditions are met, the softstarter action is based on the setting for (OIL):
OIL = ALA will activate an alarm by internal bit or relay output (set r3 = AIL).
OIL = dEF will fault the softstarter and display code OLC.

슈나이더 일렉트릭 Korea

도움이 필요하신가요?

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.