How is damper control configured on the ATV212 series drive?
Issue:
Damper control configuration on the ATV212 series drive
Product Line:
Altivar 212 series drives.
Environment:
All models and serial numbers with firmware revision 1.5 or greater.
Cause:
Damper control configuration assistance needed with this drive.
Resolution:
Damper control on the ATV212 drive requires 3 settings to be adjusted. You need to configure a relay output to control the damper, then you need to configure a logic input to monitor the damper status via the damper end switch, and finally the parameter F580 needs to be configured for the type of feedback switch your damper has. See details from the ATV212 Programming manual below:
NOTE: Damper Control in the enclosed ATV212 S-Flex drive package is managed differently. Consult the S-Flex documentation for details.
Damper control configuration on the ATV212 series drive
Product Line:
Altivar 212 series drives.
Environment:
All models and serial numbers with firmware revision 1.5 or greater.
Cause:
Damper control configuration assistance needed with this drive.
Resolution:
Damper control on the ATV212 drive requires 3 settings to be adjusted. You need to configure a relay output to control the damper, then you need to configure a logic input to monitor the damper status via the damper end switch, and finally the parameter F580 needs to be configured for the type of feedback switch your damper has. See details from the ATV212 Programming manual below:
NOTE: Damper Control in the enclosed ATV212 S-Flex drive package is managed differently. Consult the S-Flex documentation for details.
게시 대상: 슈나이더 일렉트릭 Korea


도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.