오늘 무엇을 도와드릴까요?

Video: How do I change the analog input AI2 on the ATV61 or ATV71 to accept 0-10Vdc instead of 4-20mA?

Article available in these languages:

  • 핀란드어

Issue:
Changing the analog input AI2 on the ATV61 or ATV71 to accept 0-10Vdc instead of 4-20mA.

Product Line:
Altivar 61, Altivar 71

Environment:
All Serial Numbers

Cause:
Programming and wiring of an analog input AI2.

Resolution:
Go into Drive menu and then 1.5 Inputs/Outputs menu.
Go into AI2 submenu and change AI2 type to voltage.
Min and max values can be adjusted as needed.  Example would be min 0vdc and max 10vdc.



If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings