Can I use a different line voltage than what my drive is rated for?
Issue:
Different line voltage usage for Altivar Drives.
Product Line:
Altivar drives
Environment:
All models
Cause:
None
Resolution:
Drives that are rated for a specific line voltage range should only be operated within that range. Attempting to operate a drive outside this range will result in an under supply fault or over supply fault.
Line voltage tolerance is +10% and -15%.
For example: With a 460V drive the line voltage tolerance range would be 391VAC to 506VAC.
Different line voltage usage for Altivar Drives.
Product Line:
Altivar drives
Environment:
All models
Cause:
None
Resolution:
Drives that are rated for a specific line voltage range should only be operated within that range. Attempting to operate a drive outside this range will result in an under supply fault or over supply fault.
Line voltage tolerance is +10% and -15%.
For example: With a 460V drive the line voltage tolerance range would be 391VAC to 506VAC.