브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
BMXAMI0410 LED's - RUN, IO, ERR, and DL may blink simultaneously following a firmware upgrade
Issue
Upgrading the firmware in a BMXAMI0410 module from version 1.00 to any higher version may cause the RUN, IO, ERR, and DL LED's to blink simultaneously after the upgrade has completed.



Product Line
BMXAMI0410



Resolution
The issue is caused by a bug in version 1.0 only.  When upgrading to any newer version from version 1.0, the blinking LED pattern may occur.  Although Unity Loader will display a message the upgrade was successful, a power cycle of the module or rack it is mounted in will resolve the LED's blinking.

If the BMXAMI0410 firmware is already at a version 1.1 or higher and another upgrade is required, the blinking LED pattern will not occur after the upgrade is completed.


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings