What are the limitations of the Modbus TCP IO Scanner of a TM251MESE?
The limitation of the Modbus TCP IO Scanner of a TM251MESE are:
- maximum 64 channels divided between maximum 64 slaves.
Each channel has the following limitations:
- for Read/Write Holding Registers the maximum length is 125 read words and 121 write words
- for Read Holding Registers the maximum length is 125 words
- for Write Multiple Registers the maximum length is 123 words
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
게시 대상: 슈나이더 일렉트릭 Korea

