What can cause an CFF fault on the ATV12 drives?
Issue:
CFF fault on the ATV12 drives?
Product Line:
Altivar ATV12
Environment:
All
Cause:
Drive is powering up with an CFF fault and will not clear.
Resolution:
CFF= incorrect configuration fault.
Possible causes:
-HMI block replaced by and HMI block configuration on a drive with a different HP ratings.
-The current parameter of the customers parameter is inconsistent.
Remedy: Try resetting the drive back to a factory default by going into:
ConF menu enter
FCS menu enter
change FCS menu to InI and hold for 2 seconds.
Now power cycle the drive.
If the fault clears, now try and reprogram the drive. If you are still getting the CFF fault then you will need to replace the drive.
CFF fault on the ATV12 drives?
Product Line:
Altivar ATV12
Environment:
All
Cause:
Drive is powering up with an CFF fault and will not clear.
Resolution:
CFF= incorrect configuration fault.
Possible causes:
-HMI block replaced by and HMI block configuration on a drive with a different HP ratings.
-The current parameter of the customers parameter is inconsistent.
Remedy: Try resetting the drive back to a factory default by going into:
ConF menu enter
FCS menu enter
change FCS menu to InI and hold for 2 seconds.
Now power cycle the drive.
If the fault clears, now try and reprogram the drive. If you are still getting the CFF fault then you will need to replace the drive.
게시 대상: 슈나이더 일렉트릭 Korea


도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.