What is the difference between a rectifier and a standard transformer in Oil Distribution Transformers?

There is nothing special on the mechanical part (the tank) in Oil Distribution Transformers. However the electrical design, the active part differs compared to a standard transformer. Power electronic circuits can convert alternating current (ac) to direct currents (dc). These are called rectifier circuits. The vice versa is also applicable in a power circuit which is called inverter circuits. A transformer that has one of its windings connected to one of these circuits is considered to be a converter or a rectifier transformer. Electronic circuits provide many types of control today, and they are getting more and more in practice. These circuits are generally more efficient than previous types of control. Rectifier circuits are used to provide high-current dc for electromechanical process like chlorine production as well as copper and aluminium production. They are also used in variable-speed-drive motor controls, transit-traction applications, mining applications, electric furnace applications, higher-voltage laboratory-type experiments, high-voltage direct-current power transmission (HVDC) static precipitators, and others. The operation of the semiconductor rectifier produces harmonic voltages and currents. The harmonic currents are at higher frequencies than the fundamental frequency of the transformer. The problem is coming from the harmonic current. These higher-frequency currents cause high levels of eddy-current losses and other stray losses in other parts of the transformer. This can create potentially high temperatures, which degrade the insulation of the transformer and can cause earlier failure of the transformer. So the idea is to do such a design that will withstand and overcome those affects that are generated by the harmonic currents. We usually limit the flux density and the current density at a certain level and integrate an electrostatic shield between the primary and the secondary windings. A rectifier transformer has a bigger footprint, is heavier and is more expensive compared to a standard transformer.

슈나이더 일렉트릭 Korea

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings