How do we display the recipe label without using the toolchest object?

Issue:
How do we display the recipe label without using the toolchest object?

Product Line:
Vijeo Designer (all versions)

Resolution:
To display the recipe label without using a toolchest object, simply create a String display and point to the system variable _RecipeControlDefault.RecipeLabel

NOTE: Ensure that your variable filter is set to None in order to show all the variables available in the variable list.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.