오늘 무엇을 도와드릴까요?

Executing the ETL returns the error "No usable Plugin loaded"

Issue
After downloading and unzipping the ETL tool to the desired installation folder, the error "No usable Plugin loaded" is returned when
the TacticalSolutionsManager.exe is launched to begin utilizing the ETL configuration tool.

ETL_usable_plugin_error

Product

Power Monitoring Expert 7.2.x

Power Monitoring Expert 8.x

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024



Environment
ETL Tool

Cause
This error is usually because the file you have downloaded (zipped/compressed file) has been "blocked" by Windows because it came from the internet.
This is a common issue for people downloading files from the Internet. (Note: this could apply to any downloaded zipped/compressed file containing executable code)

Resolution
The downloaded file must be "unblocked" before unzipping it to the desired ETL installation folder.
To unblock it, access the zipped/compressed file's properties (e.g., right-click and select Properties) and then press the Unblock button.
Then press the OK button.  Delete the original ETL installation folder and unzip the file to a folder as before.

ETL folder properties settings

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings