How to program the ATV71 drive to run from local control (keypad)?
Issue:
How to program ATV71 to run from local control?
Product Line:
Altivar 71, ATV71
Environment:
All
Cause:
N/A
Resolution:
Select the Drive menu.
Go to 1.6 Command, menu.
Set Ref 1 channel to HMI.
Set Profile to Not Separate.