브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How can we have diagnostic information for TMC2xxx additional cartridge analog I/O module within a TM221Cxxx PLC SoMachine/Machine Expert - Basic application program ?
Within TM221Cxxx PLC and SoMachine/Machine Expert - Basic, we have the possibility to add 1 or 2 optional cartridges (depending on the TM221Cxxx PLC reference). Such cartridge provides 2 analog inputs or outputs channels as extension for the M221 PLC local I/Os.

For each channel, it exists a dedicated system word object available for diagnostic .
It’s  %IWS.0.i  for an analog input channel
It’s %QWS.0.i  for an analog output channel

With i defined by this way:
i=100  for  the 1st channel of the cartridge located 1st slot
i=101  for  the 2nd channel of the cartridge located  1st slot
i=200  for  the 1st channel of the cartridge located 2nd slot
i=201  for  the 2nd channel of the cartridge located 2nd slot

The definition of the code status/diagnostic value is as below:

For %IWS word content definition
0Normal
1Data conversion in progress
2Initialization in progress
3Input operation setting error or module without input
4not used
5High limit  reached
6Low limit reached
7Non-volatile memory error

For %QWS word content definition
0Normal state
1not used
2Initialization in progress( after power on)
3Output operation setting error or module without output
4not used
5not used
6not used
7Non-volatile memory error

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings