What is the firmware upgrade procedure of M580 CPU ?

M580 now has 2 hardware versions. Those 2 versions are differentiated by their color. The newer versions come in "grey" color, while the old ones come in "white".

Based on it, the upgrade procedure of both hardware versions differ. The old "white" one used to get upgraded by "Unity Loader" tool. However recently, Schneider Electric released a newer tool called "EADM > EcoStruxure Automation Device Maintenance". This tool "EADM" is now responsible for the firmware upgrade/update of numerous products, where M580 is one of them.

In that regard, both versions' firmware can get upgraded/updated by "EADM", whereas the grey versions cannot get upgraded/updated by "Unity Loader". Consequently, it is highly recommended to use "EADM" for M580 firmware upgrade/update.

The most important point to remember is that starting from firmware version V4.10, the upgrade/update requires 2 steps to be performed :

  1. To upgrade the old firmware V3.3x (or earlier) to an intermediary V3.99 - Migration Firmware version
  2. Then upgrade the intermediary V3.99 - Migration Firmware version to the intended V4.xx Modicon M580 Secure Firmware one

Old firmware V3.3x versions are of ".LDX" extension, while V4.xx versions are of ".SEDP" one

For more info, kindly refer to the below docs :

  • "Modicon M580 Controller Firmware Installation Guide"/doc no. "EIO0000004992"
  • "Modicon M580 Controller Firmware History"/doc no. "RN0000000110"
  • "EcoStruxure Automation Device Maintenance Firmware Upgrade Tool Online Help"/doc no. "EIO0000004033"

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings