오늘 무엇을 도와드릴까요?

How to Import Logical Device Templates for EM4800 and BCPM in PME 7.2.2 and PME 8.x?

Issue

How to import Logical Device Templates for EM4800 and BCPM into current versions of Power Monitoring Expert.

Product Line

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

Logical Device Templates

EM4800

BCPM

Management Console

Cause

The Logical Device Template was created using an older driver source (for example, SPM 7.0.1 or older PME driver sets).
These templates are not directly compatible with newer PME systems because the Logical Device Type definitions and measurement sets differ across versions.

Resolution

To import the Logical Device Template into PME:

  1. Identify the origin of the template

    • Templates created using SPM 7.0.1 or other legacy driver versions cannot be imported directly into modern PME systems.
  2. Create a new Logical Device Type in PME

    • Open Management Console.
    • Navigate to Tools → Logical Device → Logical Device Type Editor.
  3. Define all required measurements

    • Review the Logical Device Template’s Output Measurement column (column F).
    • Examine any circuit (e.g., Circuit 01 or Circuit 02).
    • All circuits use the same measurement set.
  4. Build the Logical Device Type

    • Add all the measurements supported by each circuit (such as Current, Voltage, energy metrics, etc.).
  5. Import the Logical Device Template into PME

    • Once the Logical Device Type is created, the template can be imported successfully.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support information


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings