오늘 무엇을 도와드릴까요?

RealTime table for BCPM is reading kWh not AMPS in ION setup

Issue
Customer is trying to read real time current data from BCPM using ION setup real time table, However ION setup is showing kWh readings in the AMPS column

Product Line
BCPM

Environment
​ION Setup 3.0

Resolution

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

As of 4/14/2016 with latest release of ION Setup V3.0.16091.01, RealTime.pml files are mapped incorrectly to read kWh registers instead of currents readings.
Those RealTime.pml files are located inside all the templates folders in ION setup installation folder for BCPM meters
...\Schneider Electric\ION Setup\Tables\BCPM\

Those files are looking for kWh floating registers starting at 42000 when they are supposed to be looking for currents floating registers starting at 42252

To fix this issue, download BCPM_RealTime.zip from below and replace RealTime.pml inside each folder with the corresponding file inside ION setup installation folder

Note: This issue is resolved in the future release of ION Setup.

슈나이더 일렉트릭 Korea

첨부 파일
BCPM_RealTime.zip [8.4 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings