오늘 무엇을 도와드릴까요?

Control Expert (formerly Unity Pro) error message: "Exchange list generation fail : Code generation failure"

Article available in these languages:

  • 스페인어

Issue:
The user is editing online and receives the error and cannot proceed with a "Build changes" or "Rebuild All Project".

Environment:
Control Expert/Unity Pro software online with a PLC.

Resolution:
A change has been made that should be made in offline mode.
It requires disconnecting and performing a "Rebuild All" followed by a download.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings