오늘 무엇을 도와드릴까요?

What is the replacement for the Magelis XBTGT7340?

Issue:
The Magelis XBTGT7340 is no longer in production. What is its replacement?

Product Line:
Magelis HMI, Magelis XBTGT series

Resolution:
The replacement for the Magelis XBTGT7340 can be one of two models depending on the need for video or multi-media support.
If video support is not required, use the combination: HMIG3U (Premium BOX CPU module) together with the HMIDT732 (15" touchscreen that snaps onto the front of the CPU module).
If video support is required, use the combination: HMIG5U22 (Open BOX CPU module) together with the HMIDT732 (15" touchscreen that snaps onto the front of the CPU module).

NOTE: The old application designed for the XBTGT7340 can be used with either the HMIG3U or HMIG5U22 with little modification. Generally we only need to switch the Target Type and Target Model. In rare occasions, some I/O driver settings may need to be updated.

The required software to program the HMIG3U is Vijeo Designer 6.2 SP5 or greater. Please update the software. The latest service pack for Vijeo Designer 6.2 is SP12 (Service Pack 12).

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings