브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Does Control Expert (formerly Unity Pro) offer a way to detect if an ERIO drop has a problem on one or more of its IO modules?

Issue:

Does Control Expert (formerly Unity Pro) offer a way to detect if an ERIO drop has a problem on one or more of its IO modules?

Product Line:

Control Expert, Unity Pro, ERIO drop

Resolution:

Yes, the following System Words can be used to determine module health in an ERIO drop.

%SW152-153  Referred to as ERIO_Drop_Status
0=There is a problem with one or more modules in this drop
1=Drop status is good, no IO problems in this drop


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings