브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Video: Why does the Local/Remote button not work on the Process drive keypad?

Article available in these languages: 핀란드어

Issue:
Local/Remote button does not work

Product line:
Altivar 600 Family: ATV630, ATV650, ATV660, ATV680
Altivar 900 Family: ATV930, ATV950, ATV960, ATV980

Environment:
All

Cause:
Default programming

Resolution:
The factory setting for Process drives' Local/Remote button is 'deactivated'.
To activate it:
  1. go to menu 5: Complete Settings (CSt-)
  2. go to menu 5.5 for ATV600: menu 5.4 for ATV900: Command and Reference (CrP)
  3. go to parameter HMI cmd. (bMP) and change it from Deactivated (diS) to Bumpless (buMP) or to Stop.
Bumpless means that if transitioning from Remote to Local the drive will continue in it's last state...so if it was running, it will continue to run at the same speed, but can now be controlled by the keypad in local mode.  When changing from local back to remote the drive will only run if the remote controls are calling for it to run and it will automatically switch to the remote speed reference.
Stop means that the drive will be stopped when switching between Local and Remote and a new run command will be required.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings