How to copy alarm messages between Vijeo Designer applications?
Issue:
How to copy alarm messages between Vijeo Designer applications?
Product Line:
Vijeo Designer
Resolution:
The alarm messages are embedded in the variables. To copy the alarm messages between two identical project, export the variables from one project and import it into the other project. Assuming that the variables name are the same.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.