Does the M580 Hot Standby CPU's support %SW60 - 65 and %SW69 ?

Issue:

Does the M580 Hot Standby CPU's support %SW60 - 65 and %SW69 ?

Product Line:

M580 Hot Standby

Resolution:

No. These words are dedicated to the Unity Quantum HSBY solution.
The M580 uses a DDT (Device Data Type) which is automatically created when selecting an M580 HSBY processor in Control Expert (formerly Unity Pro)..

The DDT is named ECPU_HSBY_1. All of the functionality and status information offered by %SW60 - 65 for Quantum HSBY is made
available through this DDT for M580 HSBY user.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team