How to set Analog Output in I/O expansion board to use 4-20 mA instead of 0-20mA?

Title
Analog Output Scaling Formula and Calculation Method for Zero Scale and Full Scale

Language
English

Issue
Users need to calculate Zero Scale and Full Scale values when configuring analog outputs whose hardware output ranges differ from the receiving device’s expected input range.

Product Line
ION Meters
PM8000 Series
ION9000 Series
ION Setup
I/O expansion board

Environment
Meter configuration using ION Setup
Analog Output scaling

Cause
Analog output scaling settings must be calculated when the meter’s analog hardware output range does not match the receiving device’s signal range.

Resolution
The analog output module uses a linear relationship between the Source input and the hardware output. Scaling requires defining the minimum and maximum hardware output values and computing the corresponding Zero Scale and Full Scale values.


Image

Definitions:
Aa = analog hardware output minimum range value
Af = analog hardware output maximum range value
Ax = analog hardware output minimum value
X = scaled equivalent of Aa

The mathematical relationship between the values is shown by the following equation:

(FullScale – X) / (FullScale – ZeroScale)  =  (Af – Aa) / (Af – Ax)

Example
A meter monitors a 0–120 kW system.
The receiving device requires 4–20 mA.
The meter’s analog output hardware range is 0–20 mA.

Variables:
FullScale = 120
X = 0
Af = 20
Ax = 0
Aa = 4

From the scaling equation, Zero Scale = −30
Full Scale = 120

These values produce a 0–120 kW output represented as a 4–20 mA analog signal.

After connecting to your meter in ION Setup, open setup assistant and navigate to Analog Out and choose which output you want to configure.
You can configure the Source, Zero Scale, Full Scale, and port to use for that Analog Output as below:


Setup Assistant

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings